Mould growth in buildings
Contents |
[edit] Introduction
TG 26 Mould in Buildings, A BSRIA topic guide, written by Spyros Efthymiopoulos & Yasemin D. Aktas, and published by BSRIA in 2024, states: 'Mould is a subcategory of the fungal kingdom. It is broadly composed of spores and filaments, known as hyphae as shown in the image below. These collectively form a filamentous network called mycelium. Mould is ubiquitous in indoor and outdoor environments. As a large portion of the fungal kingdom, moulds account for thousands, if not millions, of known and unknown species.'
Mould (sometimes referred to as mildew) is a fungal growth. Whilst mould itself is not toxic, some moulds can produce toxins that can have negative effects on human health, for example causing asthma, rhinitis, itchy eyes, respiratory symptoms, respiratory infection and eczema.
Mould in buildings can be visible or can be hidden, but it is generally an indication of a defect such as thermal bridging, condensation, leaks or penetrating or rising damp.
Mould requires four factors for growth:
- Mould spores.
- Food.
- Appropriate temperature.
- Moisture.
[edit] Spores
Mould spores are microscopic (ranging from 3 to 40 microns) and ubiquitous in the environment. Mould spores can be found floating in the air and in normal house dust. It is not generally practical therefore to eliminate mould spores and this is not a strategy for controlling mould growth.
[edit] Food
Mould will feed on any substance that contains carbon atoms (such as organic substances). Many of the natural materials found in the built environment provide suitable food for mould, such as timber and paper. Removing sources of food for mould from an environment is generally impractical.
[edit] Appropriate temperature
The majority of moulds grow well in a range of temperatures similar to those that humans require. This temperature range is wide, and even temperatures close to freezing will not prevent growth. In warmer environments, moulds will thrive. It is generally impractical therefore to control mould growth through temperature.
[edit] Moisture
Most moulds require relatively high levels of moisture in order to grow. The majority require an equivalent of at least 70% relative humidity to thrive and most large mould outbreaks in buildings, occur where porous, cellulose-type materials contain persistent liquid water or condensation.
Humans typically prefer humidity levels below 70% and so limiting moisture availability and killing and removing active mould colonies is generally the easiest method of control.
For more information, see Moisture.
[edit] Methods for reducing moisture levels
In Europe, depending on the country, it is estimated that between 10% and 50% of buildings are damp (ref. WHO Europe, Damp and mould, Health risks, prevention and remedial actions 2009).
Moisture levels can be reduced through a number of measures:
- Natural or mechanical ventilation.
- Use of de-humidifiers or air conditioning units.
- Insulation of cold surfaces, such as pipes.
- Increasing air temperature.
- Removing sources of moisture such as drying clothes and ensuring vented tumble dryers are appropriately vented to the outside.
- Mending leaking pipes, wastes and overflows.
- Eliminating rising damp and penetrating damp.
[edit] Related articles on Designing Buildings
- Approved Document C.
- Aspergillus.
- BSRIA topic guide on mould in buildings TG 26/2024.
- Condensation.
- Damp and timber report.
- Damp proofing.
- Degradation of construction materials.
- Dry rot fungus.
- Humidity.
- Mould inspection.
- Moulds in historic buildings.
- Moisture.
- Penetrating damp.
- Recognising wood rot and insect damage in buildings.
- Rising damp.
- Rising damp in walls - diagnosis and treatment (DG 245).
- Stachybotrys.
- Wet rot.
[edit] External references
Featured articles
Check out some of the best features and news from Designing Buildings as well as key stories from around the web.
The importance of early engagement
Construction lessons from the Trillium HealthWorks Experience Centre.
Mayors are to be given planning call in powers
Mayors across England will be able to make the most important planning decisions.
The Master Builder: William Butterfield and his times. Book review.
Why construction can't afford to ignore the skills gap.
Building Safety Regulator, 19 August
Gill Kernick appointed Independent Chair of Residents’ Panel.
Connecting knowledge, technology and conservation
Building competence for the future of built heritage.
Building Regulations and Building Safety Act
CIOB publishes free advice for non-domestic clients.
Building Safety Newsletter from MHCLG.
An extraordinary record of steel engineering worldwide.
Households living near new pylons to save on bills.
ECA warns growth must not outpace grid capacity or skills.
The role of the client and decision making
CIOB response to built environment professions call for evidence.