Last edited 14 Jan 2022

Minimum efficiency reporting value MERV

Contents

[edit] Introduction

The minimum efficiency reporting value (MERV) can be used to evaluate the effectiveness of air filters in heating, ventilation and air conditioning (HVAC) components.

[edit] Background

The rating system was developed in the 1980s by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). ASHRAE develops standards related to refrigeration processes and the design and maintenance of indoor environments. The purpose of the organisation's standards is to establish consensus for test use in commerce as well as performance criteria for use as facilitators.

This MERV rating system is used in the US for comparing air filters made by different manufacturers. It assigns a single number air filter designation based on how well it captures and holds dust. MERV rated filters may be used in place of high efficiency particulate arrestance (HEPA) or ultra low particulate air (ULPA) filters in certain circumstances (such as when central air conditioning systems are in place).

[edit] MERV testing

The MERV rating system is based on ASHRAE Standard 52.2-2007, the testing protocol for air filtration performance.

It reflects a measurement of the filter’s arrestance - or its ability to remove dust from the air - relative to how many of a specific size dust particle (within the range of 0.3 to 10 micrometers) need to be removed to keep HVAC equipment clean.

The test extends over six cycles and begins with a clean filter. During each cycle, a measured amount of particles (broken down into three size categories) is released into the test airstream. These three arrestances are:

  • E1 for small particles such as tobacco smoke and bacteria.
  • E2 for medium size particles such as welding fumes.
  • E3 for larger particles such as dirt, lint, hair and dust.

The number of particles trapped and missed is measured. This procedure is repeated five additional times and the MERV rating is calculated based on the poorest performance rating during the six tests.

The MERV number corresponds to the filter’s efficiency in its clean, least efficient state (which is why the rating is referred to as ‘minimum efficiency’). A filter increases in efficiency as it loads.

[edit] Explanation of ratings

MERV values range from 1 (minimal filtering) to 16 (maximum filtering).

Mid-range rated filters (from 7 to 13) are typically recommended for commercial buildings. During the new construction phase, MERV 8 filters may be advisable, with MERV 13 filters generally recommended once the building is operational.

BSRIAIAQTable3.jpg

(NB: MERV 17-20 ratings are no longer acknowledged by ASHRAE.)

Sample rating ranges include:

Originally, MERV values ranged from 1 to 20, but ASHRAE stopped recognising MERV values from 17 to 20 in January 2009. This range is instead represented by HEPA and ULPA filters, which are capable of removing extremely high levels of dust particles as well as some viruses and other dangerous airborne particulates.

[edit] The impact of air resistance on MERV

In a furnace or air handler, the queuing up of air to pass through a high-MERV filter creates resistance. Referred to in HVAC language as a pressure drop, this condition decreases airflow on the downstream side of the air filter.

Pressure drop may increase as the MERV number increases. As contaminants load on the filter, pressure in the system rises and can have a negative impact on airflow. This may cause systems to operate for longer periods of time in order to reach certain temperature settings. In extreme cases, decreased airflow over the part of the system that heats (in winter) or cools (in summer) can lead to overheating and an automated system shutdown or icing over of the coil.

[edit] Related articles on Designing Buildings